Many instrument false alarms and inaccurate readings are not caused by faulty hardware. In most cases, the root cause is incorrect zero and span configuration or poor calibration. This guide focuses on the widely used 4–20 mA transmitters, explains core definitions, standard calibration workflows, common field mistakes, and troubleshooting tips for process instruments.
Key Takeaway: Zero and span interact with each other. The correct calibration sequence is always: Calibrate Zero FIRST, then Span. Reversing this order will invalidate your calibration results.
The zero point represents the starting reference point of the measurement range of an instrument. For a standard 4–20 mA transmitter, zero corresponds to the 0% measurement value, which should output a steady 4 mA signal.
Example: For a 0~100 kPa pressure transmitter, zero means the process pressure = 0 kPa, expected output = 4 mA. If the transmitter outputs a value higher or lower than 4 mA when the real measured value is zero, this condition is called zero drift. Zero drift will create a fixed offset error across the entire measurement range.
Span refers to the full measurement span (the difference between upper range value and lower range value) of the instrument.
Important note: Span is NOT equal to the upper range limit. It is the total width of the measuring interval.
For the same 0~100 kPa transmitter:
If you reconfigure a transmitter from 0–100 kPa to 20–80 kPa, the new span becomes 60 kPa. The 4 mA output now corresponds to 20 kPa and 20 mA corresponds to 80 kPa.
| Item | Zero (Zero Point) | Span |
|---|---|---|
| Definition | The 0% reference point of the measurement range | The total width between LRV and URV |
| 4–20mA Signal | Fixed reference: 4 mA | Signal span: 16 mA (20mA minus 4mA) |
| Error Impact | Creates constant offset on all readings | Changes the slope / sensitivity of measurement |
| Calibration Order | Adjust first | Adjust after zero calibration |
| Similar Concept Reminder | Related to zero shift / zero migration | Related to measurement sensitivity |
⚠️ Critical distinction: Zero Migration is NOT changing span. Migration only shifts the zero point left or right; the span value stays unchanged. Example: A transmitter with range 0~100 kPa (span=100 kPa) can be migrated to -20~80 kPa. The span remains 100 kPa, only the zero reference moves.
Zero and span are interactive parameters. Adjusting one will affect the other, so follow this standard procedure strictly.
Warm up the instrument Power on the transmitter and let it stabilize for 10–15 minutes before calibration. Electronic sensors need time to reach stable working temperature to avoid thermal drift.
Prepare zero condition, calibrate zero Remove process pressure / input signal, bring the measured variable to the true zero condition. Confirm no residual pressure, static pressure or process medium acts on the sensor. Adjust zero until the output signal is exactly 4 mA.
Apply full-span input signal, calibrate span Feed the certified 100% input value (full upper range value). Adjust the span setting until the transmitter output reads exactly 20 mA.
Cross-check and repeat iteration After one round of zero + span adjustment, the zero point will usually shift slightly. Go back to zero condition and recheck zero, then recheck full span. Repeat 1–2 cycles until both points hold stable.
Three-point verification before commissioning Test these three standard points to confirm linear performance:
These mistakes are the top reasons for unstable readings and unexpected alarms.
❌ Mistake 1: Only adjust span, skip zero calibration Symptom: All measured values carry a fixed offset. Even if full scale looks correct, every reading is biased.
❌ Mistake 2: Choose an unnecessarily large span A wider span reduces measurement resolution. Small real fluctuations in your process signal will be hidden, and the instrument cannot capture subtle process changes. Select the minimal required span that covers your normal working range.
❌ Mistake 3: Perform zero calibration under loaded / live process conditions Calibrating zero with pressure, liquid head or static pressure applied introduces permanent static error. Always isolate, vent or drain the sensor to get a true zero state.
❌ Mistake 4: Confuse zero migration with span adjustment Migration only translates the measuring range. It does not change the instrument sensitivity or span. If you need to modify the measuring interval width, you must reconfigure span parameters.
❌ Mistake 5: Skip post-calibration multi-point verification Many technicians only check 0% and 100%. Non-linearity errors at 50% may remain hidden and trigger intermittent alarms.
Schedule a full zero and span calibration in these scenarios:
Zero and span are the foundation of accurate 4–20 mA analog measurement. Most instrument troubleshooting should start with zero and span verification before replacing hardware. Mastering the calibration sequence and avoiding the above common pitfalls will greatly reduce false trips and improve process measurement reliability.